Description
Toggle relay for alternating control of 3 electropumps, with high sewage level control
Control signals by closing contact, pressure switch and internal timing
Designed to be used in sewage, with RNC1002 sewage level regulator
Applications
- Alternate command of three electric pumps and control of lack of water in the supply network
- Control signals by closing contact, pressure switch and internal timing
- Alternating voltage for water supply probe
Operation
Power the relay (green led on – A.1)
The closing of the contact pair “RN0” (4 – 6) leaves the relay in standby mode. If the pairs of contacts “RN1” (5 – 6) and “RN2” (7-6) and “RN3” (8 – 6) close, they will force the operation of the sewage pumps one, two and three, respectively.
If the contact pair “RN3” (8-6) is closed, the high level alarm signal “N.A.” lights up. The alarm goes off when the “RN3” (8-6) contacts open.
The three electric pumps only switch off after the contacts “RN3” (8 – 6), “RN2” (7 – 6), “RN1” (5-6) and “RN0” (4-6) open, To run until “RN0” (4 – 6) is open.
Terminal 1 is common to relay outputs 3, 9 and 11 for controlling the motors, respectively.