Filling control relay in tanks with alarm – RFA 101 DEP

Since (without VAT): 22.35

Filling Control Relay for tanks

Shipping is only available for Continental Portugal Shipping and its respective Autonomous Regions: Azores and Madeira.

Description

Filling control relay in tanks with alarm by minimum level.Level control in conductive liquids
Level filling control for tanks or cisterns
Adjustable sensitivity, according to the liquid conductivity (selected in the front button) 4 – 30 KΩ
Protection of pumps, against lack of water inside the tanks – alarm function for minimum level


Applications

• Level control in conductive liquids, using 3 level probles (minimum, maximum and mass ), with high level protection against tank spills

• Level filling control for tanks or cisterns

• Adjustable sensitivity, according to the liquid conductivity (selected in the front button) 4 – 30 KΩ

• Protection of pumps, against lack of water inside the tanks – alarm function for minimum level


Operation

Power the relay ( green led light on – A.1)

The output contact S1 arms when the liquid level reaches the minimum level probe (output 6) – red light switches on “F.A. – Lack of water”, indicating the absence of water inside the tank

The output contact S1 disarms when the liquid level reaches the maximum level probe (output 5) – red light switches off

Note: The images shown may not correspond completely to the product described.

Additional information

Weight 190 g
Dimensions (D x W x H) 7.5 × 3.5 × 8 cm
Sensibilidade regulável

4 a 30 KΩ

Temperatura ambiente

[-10ºC, +55ºC]

Relé de saída

AC 8A-250V / 50Hz – 1250VA DC 5A-24 V (C.R.)

Alimentação

AC (24V, 230V, 400V) / 50Hz

Consumo

2VA (approx.)

Tensão

24V AC, 230V AC, 400V AC

Encaixe

11-pin base